AWG to mm² Converter
Convert between AWG, kcmil and mm² from the AWG definition and see the nearest standard sizes.
The definition
d(n) = 0.127 mm × 92^((36 − n) ÷ 39) A = π × d² ÷ 436 AWG is 0.005 in (0.127 mm) and 4/0 is 0.46 in, with 39 equal steps between them. Sizes 1/0 to 4/0 are n = 0, −1, −2, −3. One kcmil is 1000 circular mils, which is 0.506707 mm².
AWG sizes calculated from the definition
| Size | Diameter (solid) | Area | Next metric size up |
|---|---|---|---|
| 24 AWG | 0.511 mm | 0.2047 mm² | 0.5 mm² |
| 23 AWG | 0.573 mm | 0.2582 mm² | 0.5 mm² |
| 22 AWG | 0.644 mm | 0.3255 mm² | 0.5 mm² |
| 21 AWG | 0.723 mm | 0.4105 mm² | 0.5 mm² |
| 20 AWG | 0.812 mm | 0.5176 mm² | 0.75 mm² |
| 19 AWG | 0.912 mm | 0.6527 mm² | 0.75 mm² |
| 18 AWG | 1.024 mm | 0.823 mm² | 1 mm² |
| 17 AWG | 1.150 mm | 1.038 mm² | 1.5 mm² |
| 16 AWG | 1.291 mm | 1.309 mm² | 1.5 mm² |
| 15 AWG | 1.450 mm | 1.65 mm² | 2.5 mm² |
| 14 AWG | 1.628 mm | 2.081 mm² | 2.5 mm² |
| 13 AWG | 1.828 mm | 2.624 mm² | 4 mm² |
| 12 AWG | 2.053 mm | 3.309 mm² | 4 mm² |
| 11 AWG | 2.305 mm | 4.172 mm² | 6 mm² |
| 10 AWG | 2.588 mm | 5.261 mm² | 6 mm² |
| 9 AWG | 2.906 mm | 6.634 mm² | 10 mm² |
| 8 AWG | 3.264 mm | 8.366 mm² | 10 mm² |
| 7 AWG | 3.665 mm | 10.55 mm² | 16 mm² |
| 6 AWG | 4.115 mm | 13.3 mm² | 16 mm² |
| 5 AWG | 4.621 mm | 16.77 mm² | 25 mm² |
| 4 AWG | 5.189 mm | 21.15 mm² | 25 mm² |
| 3 AWG | 5.827 mm | 26.67 mm² | 35 mm² |
| 2 AWG | 6.544 mm | 33.63 mm² | 35 mm² |
| 1 AWG | 7.348 mm | 42.41 mm² | 50 mm² |
| 1/0 AWG | 8.251 mm | 53.48 mm² | 70 mm² |
| 2/0 AWG | 9.266 mm | 67.43 mm² | 70 mm² |
| 3/0 AWG | 10.405 mm | 85.03 mm² | 95 mm² |
| 4/0 AWG | 11.684 mm | 107.2 mm² | 120 mm² |
Stranded cable of the same gauge can have slightly different area and overall diameter, and different nominal sizes are not interchangeable without checking voltage drop and the rating you read from the datasheet.
Questions
Is 12 AWG the same as 2.5 mm²?
12 AWG has an area of 3.309 mm², between the 2.5 and 4 mm² metric sizes, so it is not the same as either. Which one you may use depends on your datasheet and local rules.
Why does a bigger AWG number mean a thinner wire?
The AWG number counts the drawing steps used to make the wire thinner, so higher numbers are thinner. Every 3 gauge steps roughly doubles the area.
Where do the standard metric sizes come from?
The series 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240, 300 mm² is a list of nominal conductor areas defined by IEC 60228.
Sources and constants
- ASTM B258, standard nominal diameters and cross-sectional areas of AWG sizes (the standard itself is paywalled and is not reproduced here)
- IEC 60228, conductors of insulated cables (the standard itself is paywalled and is not reproduced here)
Related
Get the app
Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.
Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.