Voltage Drop Calculator (DC, 1-Phase, 3-Phase)

Voltage drop is the voltage lost along the conductors: V_drop = k × I × R. Enter the one-way run length and the return is included.

Calculator

System
Presets only; check your local supply.
The return conductor is included automatically.
Resistance is corrected from 20 °C.
Your choice, not a standard.
Advanced: use a resistance from the cable datasheet
Leave empty to compute from size and material. Temperature correction still applies.

Formula

V_drop = k × I × R    R = ρ(T) × L ÷ A    ρ(T) = ρ20 × (1 + α × (T − 20))

R is the resistance of one conductor of length L (the one-way run) and area A. The loop factor k is 2 for DC and single-phase two-wire circuits, because the current goes out and comes back, and √3 for a balanced three-phase circuit (line-to-line drop at the line current). Percent drop is V_drop ÷ source voltage × 100.

Worked examples

DC, 20 °C

12 V, 10 A, 5 m one way, 4 mm² copper. R of one conductor = 21.55 mΩ, loop resistance 0.0431 Ω. Drop = 0.431 V (3.59%), voltage at the load 11.569 V, power lost 4.31 W.

The same cable at 60 °C: resistance rises by a factor 1.1572, so the drop becomes 0.499 V (4.16%).

Three-phase, 20 °C

400 V, 32 A, 50 m, 10 mm² copper, k = √3: drop 4.78 V (1.19%).

What the result does not include

Reactance and power factor are not modelled: for AC circuits with large conductors, long runs or a low power factor the true drop can be larger than this resistance-only estimate. Connections, fuses and breakers add their own drops. Rules and recommended limits differ by country and application and are not stated here.

Questions

Why is the drop twice what I expected?

The calculator includes the return conductor. Enter the one-way run length; for DC and single-phase circuits the current travels out and back, so the loop is twice the run. See one-way or round trip.

Does conductor temperature matter?

Yes. Copper resistance rises with temperature, so the same cable drops more voltage when warm. In the example above, 20 °C gives 3.59% and 60 °C gives 4.16%.

Does it include reactance or power factor?

No. Version 1.0.0-web uses resistance only. For AC circuits with large conductors, long runs or low power factor the real drop can be higher.

Sources and constants

Constants and formulas: method, constants and changelog (engine 1.0.0-web, constants checked 2026-11-18). Found a mistake? Report a calculation error.

Related

Get the app

Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.

Coming soon to Google Play

Last reviewed 2026-11-18. Engine 1.0.0-web.

Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.