Gaugewise

Method, constants and changelog

Method

Every calculator and the app use one resistance-only model: R = ρ(T) × L ÷ A for one conductor, ρ(T) = ρ20 × (1 + α × (T − 20)), drop = k × I × R, with k = 2 for DC and single-phase two-wire and √3 for balanced three-phase. Reactance, power factor, harmonics, grouping, burial and protective devices are not modelled.

Constants

QuantityValueSource and note
Copper resistivity at 20 °C1.7241 × 10⁻⁸ Ω·mAnnealed copper standard, 1.7241 µΩ·cm (NBS Circular 31)
Copper temperature coefficient at 20 °C0.00393 per °CNBS Circular 31, Table II, 100% conductivity row
Aluminum resistivity at 20 °C2.8264 × 10⁻⁸ Ω·m (copper value ÷ 0.61)61% of the copper standard; NBS Circular 31 gives 61.0% volume conductivity and about 2.828 µΩ·cm as a good average for hard-drawn aluminum
Aluminum temperature coefficient at 20 °C0.00403 per °CCommonly quoted reference value. Not confirmed against a primary source on 2026-11-18; other sources quote about 0.0039. At 75 °C the two differ by about 0.59%
AWG diameter0.127 mm × 92^((36 − n) ÷ 39)AWG definition, ASTM B258
Metric sizes0.5 to 300 mm² (19 nominal areas)Nominal areas of IEC 60228
1 kcmil0.506707 mm²Circular mil definition
1 foot0.3048 m (exact)International foot

Real cables differ from these reference values because of stranding, plating and alloy. You can enter a datasheet resistance instead. The values are physical constants and sizes; this page reproduces no code tables.

Testing

The engine is covered by automated golden tests that compare it with an independent second implementation to a relative tolerance of 1e-9 and with hand-checkable vectors. The tests check the implementation of the formulas; they do not check conformity with any code.

Changelog

Report a calculation error.

Sources and constants

Constants and formulas: method, constants and changelog (engine 1.0.0-web, constants checked 2026-11-18). Found a mistake? Report a calculation error.

Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.