Method, constants and changelog
Method
Every calculator and the app use one resistance-only model: R = ρ(T) × L ÷ A for one conductor, ρ(T) = ρ20 × (1 + α × (T − 20)), drop = k × I × R, with k = 2 for DC and single-phase two-wire and √3 for balanced three-phase. Reactance, power factor, harmonics, grouping, burial and protective devices are not modelled.
Constants
| Quantity | Value | Source and note |
|---|---|---|
| Copper resistivity at 20 °C | 1.7241 × 10⁻⁸ Ω·m | Annealed copper standard, 1.7241 µΩ·cm (NBS Circular 31) |
| Copper temperature coefficient at 20 °C | 0.00393 per °C | NBS Circular 31, Table II, 100% conductivity row |
| Aluminum resistivity at 20 °C | 2.8264 × 10⁻⁸ Ω·m (copper value ÷ 0.61) | 61% of the copper standard; NBS Circular 31 gives 61.0% volume conductivity and about 2.828 µΩ·cm as a good average for hard-drawn aluminum |
| Aluminum temperature coefficient at 20 °C | 0.00403 per °C | Commonly quoted reference value. Not confirmed against a primary source on 2026-11-18; other sources quote about 0.0039. At 75 °C the two differ by about 0.59% |
| AWG diameter | 0.127 mm × 92^((36 − n) ÷ 39) | AWG definition, ASTM B258 |
| Metric sizes | 0.5 to 300 mm² (19 nominal areas) | Nominal areas of IEC 60228 |
| 1 kcmil | 0.506707 mm² | Circular mil definition |
| 1 foot | 0.3048 m (exact) | International foot |
Real cables differ from these reference values because of stranding, plating and alloy. You can enter a datasheet resistance instead. The values are physical constants and sizes; this page reproduces no code tables.
Testing
The engine is covered by automated golden tests that compare it with an independent second implementation to a relative tolerance of 1e-9 and with hand-checkable vectors. The tests check the implementation of the formulas; they do not check conformity with any code.
Changelog
- 2026-11-18, 1.0.0-web. First version of the website calculators.
Sources and constants
- Copper Wire Tables, NBS Handbook / Circular No. 31 (1914), NIST archive
- ASTM B258, standard nominal diameters and cross-sectional areas of AWG sizes (the standard itself is paywalled and is not reproduced here)
- IEC 60228, conductors of insulated cables (the standard itself is paywalled and is not reproduced here)
Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.