One-way or round trip: which length do you enter?
Enter the one-way run length; the current also returns, so DC and single-phase drop uses a loop factor of 2 and balanced three-phase uses √3.
Short answer
Enter the distance from the source to the load, one way. For DC and single-phase two-wire circuits the current also returns through a second conductor, so the resistance in the loop is that of twice the run. The calculators and the app add that factor of two for you and list it in the assumptions.
Why the loop counts
Voltage is lost in every conductor the current flows through. In a two-wire circuit the current leaves on one conductor and returns on the other, so both conductors drop voltage: V_drop = 2 × I × ρ × L ÷ A.
Three-phase
In a balanced three-phase circuit the three phase currents add to zero at the neutral point, so there is no separate return term. The line-to-line drop at the line current is V_drop = √3 × I × R, with R the resistance of one conductor. The loop factor is √3, about 1.732, not 2.
The size of the mistake
12 V, 10 A, 5 m one way, 4 mm² copper at 20 °C:
| Case | Drop | Percent |
|---|---|---|
| One way entered, loop included (correct) | 0.431 V | 3.59% |
| Return conductor forgotten | 0.216 V | 1.80% |
| Total length entered and doubled again | 0.862 V | 7.18% |
Forgetting the return conductor halves the answer and hides a drop of 3.59% that is above a 3% target. Entering the total cable length (10 m) into a tool that already doubles it counts the return twice and gives 7.18%.
For a three-phase example, 400 V, 32 A, 50 m, 10 mm² copper: 4.78 V (1.19%) with √3, against 5.52 V (1.38%) if the same circuit were treated as two-wire.
What to enter
| Circuit | Enter |
|---|---|
| DC or single-phase, two-wire | One-way run length; loop factor 2 added for you |
| Balanced three-phase, line-to-line | Run length of one conductor; loop factor √3 |
| Total conductor length known | Switch the app to total conductor length |
Common mistakes
- Entering the total length of both conductors into a one-way field.
- Applying the factor of two to a three-phase circuit.
- Using the length of the cable run when the conductors take a longer route.
Try it: voltage drop calculator.
Questions
Does the app let me enter the total length instead?
Yes. The app can switch to total conductor length, and the assumptions card always shows which one is in use.
Why is three-phase √3 and not 2?
In a balanced three-phase circuit the phase currents cancel at the neutral point, and the line-to-line drop at the line current is √3 times I times R.
What if only one conductor of the pair carries the current?
If a circuit really has a single current-carrying conductor with no separate return in the calculation, the loop factor is 1. Most DC and single-phase circuits have a return conductor, so check what yours does.