One-way or round trip: which length do you enter?

Enter the one-way run length; the current also returns, so DC and single-phase drop uses a loop factor of 2 and balanced three-phase uses √3.

Short answer

Enter the distance from the source to the load, one way. For DC and single-phase two-wire circuits the current also returns through a second conductor, so the resistance in the loop is that of twice the run. The calculators and the app add that factor of two for you and list it in the assumptions.

Why the loop counts

Voltage is lost in every conductor the current flows through. In a two-wire circuit the current leaves on one conductor and returns on the other, so both conductors drop voltage: V_drop = 2 × I × ρ × L ÷ A.

Three-phase

In a balanced three-phase circuit the three phase currents add to zero at the neutral point, so there is no separate return term. The line-to-line drop at the line current is V_drop = √3 × I × R, with R the resistance of one conductor. The loop factor is √3, about 1.732, not 2.

The size of the mistake

12 V, 10 A, 5 m one way, 4 mm² copper at 20 °C:

CaseDropPercent
One way entered, loop included (correct)0.431 V3.59%
Return conductor forgotten0.216 V1.80%
Total length entered and doubled again0.862 V7.18%

Forgetting the return conductor halves the answer and hides a drop of 3.59% that is above a 3% target. Entering the total cable length (10 m) into a tool that already doubles it counts the return twice and gives 7.18%.

For a three-phase example, 400 V, 32 A, 50 m, 10 mm² copper: 4.78 V (1.19%) with √3, against 5.52 V (1.38%) if the same circuit were treated as two-wire.

What to enter

CircuitEnter
DC or single-phase, two-wireOne-way run length; loop factor 2 added for you
Balanced three-phase, line-to-lineRun length of one conductor; loop factor √3
Total conductor length knownSwitch the app to total conductor length

Common mistakes

Try it: voltage drop calculator.

Questions

Does the app let me enter the total length instead?

Yes. The app can switch to total conductor length, and the assumptions card always shows which one is in use.

Why is three-phase √3 and not 2?

In a balanced three-phase circuit the phase currents cancel at the neutral point, and the line-to-line drop at the line current is √3 times I times R.

What if only one conductor of the pair carries the current?

If a circuit really has a single current-carrying conductor with no separate return in the calculation, the loop factor is 1. Most DC and single-phase circuits have a return conductor, so check what yours does.

Sources and constants

Constants and formulas: method, constants and changelog (engine 1.0.0-web, constants checked 2026-11-18). Found a mistake? Report a calculation error.