Gaugewise

Wire Size Calculator by Voltage Drop

The smallest conductor whose voltage drop stays within your target, shown in both metric and AWG sizes.

Calculator

System
Presets only; check your local supply.
The return conductor is included automatically.
Resistance is corrected from 20 °C.
Your choice, not a standard.
Multiplies the load current. 1 means none.
Optional: use ratings from your own datasheetSize is mm² by default; add AWG or kcmil, for example “10 AWG”. The calculator ships no ratings and does not store what you type.

How the size is chosen

For a target drop of p percent the minimum conductor area is A_min = k × ρ(T) × L × I ÷ (p/100 × V). The calculator then picks the smallest size in each series whose area is at least A_min. If you enter ratings from your own datasheet, the size must also meet the load current in your table, and the page tells you which of the two decided the size.

Worked example, 20 °C

12 V DC, 10 A, 5 m one way, 3% target (0.36 V). Minimum area 4.789 mm². Metric series: 6 mm² gives 0.287 V (2.39%). 4 mm² gives 3.59%, above the target. AWG series: 10 AWG (5.261 mm²) gives 2.73%; 12 AWG (3.309 mm²) gives 4.34%, above the target.

Why size is not only voltage drop

A conductor must also carry its current without overheating, and that limit comes from the cable’s datasheet or the rules where you work. This calculator contains no rating tables; if you add your own ratings above they are used as typed.

Questions

What does the optional ratings box do?

It lets you type ratings from your own datasheet. The calculator then picks the larger of the size needed for the drop target and the smallest size in your table with a rating at least equal to the design current, and shows which one decided. Nothing is stored.

Why do the metric and AWG results differ?

They are different nominal areas. The calculator shows the smallest size in each series that meets the target, and the actual drop at that size.

What if the result exceeds the largest size?

The page says so and shows how many parallel runs of the largest size would reach the target.

Sources and constants

Constants and formulas: method, constants and changelog (engine 1.0.0-web, constants checked 2026-11-18). Found a mistake? Report a calculation error.

Related

Get the app

Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.

Coming soon to Google Play

Last reviewed 2026-11-18. Engine 1.0.0-web.

Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.