Extension Cord Length and Gauge Calculator
Voltage drop, heat and the largest current for an extension cord of a given length and size.
How it works
The tool current is power divided by voltage (power factor 1). The cord is a two-conductor loop, so the drop is 2 × I × R with R the resistance of one conductor over the cord length, and the heat in the cord is 2 × I² × R. The largest current for a drop target is I_max = V_target × A ÷ (2 × ρ × L).
Worked examples, copper at 20 °C
1500 W at 120 V draws 12.5 A. Over 15 m of 1.5 mm² the drop is 4.31 V (3.59%), the tool sees 115.69 V, the cord dissipates 53.9 W (3.59 W per metre of cord), and the largest current for a 3% drop is 10.44 A.
The same 12.5 A over 50 ft of 16 AWG: drop 5.02 V (4.18%).
How much heat a cord can take depends on its construction and how it is laid out; follow the cord’s label. This calculator estimates drop and heat from resistance only.
Questions
Which length do I enter?
The length of the cord from the socket to the tool. The calculator includes both conductors.
Why does a longer cord need a thicker conductor?
Resistance grows with length and falls with conductor area, so a longer run needs more area to keep the same drop.
Does it tell me if my cord is suitable?
It does not give a verdict. It shows the drop, the heat and, if you enter the label rating, how the load compares with the rating you entered.
Sources and constants
- Copper Wire Tables, NBS Handbook / Circular No. 31 (1914), NIST archive
- ASTM B258, standard nominal diameters and cross-sectional areas of AWG sizes (the standard itself is paywalled and is not reproduced here)
Related
Get the app
Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.
Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.