Gaugewise

Extension Cord Length and Gauge Calculator

Voltage drop, heat and the largest current for an extension cord of a given length and size.

Calculator

Load
Presets only; check your local supply.
The return conductor is included automatically.
Resistance is corrected from 20 °C.
Your choice, not a standard.
Read it from the cord’s label.

How it works

The tool current is power divided by voltage (power factor 1). The cord is a two-conductor loop, so the drop is 2 × I × R with R the resistance of one conductor over the cord length, and the heat in the cord is 2 × I² × R. The largest current for a drop target is I_max = V_target × A ÷ (2 × ρ × L).

Worked examples, copper at 20 °C

1500 W at 120 V draws 12.5 A. Over 15 m of 1.5 mm² the drop is 4.31 V (3.59%), the tool sees 115.69 V, the cord dissipates 53.9 W (3.59 W per metre of cord), and the largest current for a 3% drop is 10.44 A.

The same 12.5 A over 50 ft of 16 AWG: drop 5.02 V (4.18%).

How much heat a cord can take depends on its construction and how it is laid out; follow the cord’s label. This calculator estimates drop and heat from resistance only.

Questions

Which length do I enter?

The length of the cord from the socket to the tool. The calculator includes both conductors.

Why does a longer cord need a thicker conductor?

Resistance grows with length and falls with conductor area, so a longer run needs more area to keep the same drop.

Does it tell me if my cord is suitable?

It does not give a verdict. It shows the drop, the heat and, if you enter the label rating, how the load compares with the rating you entered.

Sources and constants

Constants and formulas: method, constants and changelog (engine 1.0.0-web, constants checked 2026-11-18). Found a mistake? Report a calculation error.

Related

Get the app

Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.

Coming soon to Google Play

Last reviewed 2026-11-18. Engine 1.0.0-web.

Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.