mm² vs AWG: how the two size systems relate
mm² is an area and AWG is a gauge number that gets thinner as it grows; they do not line up, so check the area and the datasheet before you swap one for the other.
Short answer
mm² is the cross-sectional area of the conductor. AWG is a gauge number: the larger the number, the thinner the wire. The two systems do not line up, so the nearest size in one series is usually a different area from the nearest in the other.
How AWG is defined
AWG fixes two diameters and spaces 38 sizes geometrically between them: 36 AWG is 0.005 in (0.127 mm) and 4/0 (0000) is 0.46 in, 39 steps apart.
d(n) = 0.127 mm × 92^((36 − n) ÷ 39) A = π × d² ÷ 4Sizes 1/0, 2/0, 3/0 and 4/0 correspond to n = 0, −1, −2, −3. Six gauge steps multiply the diameter by 2.005, roughly 2, and three steps roughly double the area. Ten steps multiply the area by about 10.2. Larger sizes are given in kcmil (thousands of circular mils); 1 kcmil is 0.506707 mm².
Some sizes from the definition
| Size | Area |
|---|---|
| 18 AWG | 0.823 mm² |
| 16 AWG | 1.309 mm² |
| 14 AWG | 2.081 mm² |
| 12 AWG | 3.309 mm² |
| 10 AWG | 5.261 mm² |
| 8 AWG | 8.366 mm² |
| 6 AWG | 13.3 mm² |
| 4 AWG | 21.15 mm² |
| 2 AWG | 33.63 mm² |
| 1/0 AWG | 53.48 mm² |
| 4/0 AWG | 107.2 mm² |
The metric series
Metric conductors use a list of nominal areas: 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 and 300 mm² (and larger). The IEC 60228 standard defines the list; the list of values is all this guide uses from it.
Nearest is not the same
12 AWG is 3.309 mm², between 2.5 and 4 mm². 10 AWG is 5.261 mm², between 4 and 6 mm². Choosing the next size up, or the nearest, changes the voltage drop and the rating you read from the datasheet. Use the datasheet of the cable you will actually buy.
Common mistakes
- Treating 12 AWG and 2.5 mm² as interchangeable.
- Reading a larger AWG number as a larger wire.
- Using the area of a solid wire for a stranded cable without checking its datasheet.
Try it: AWG to mm² converter.
Questions
How do I convert mm² to AWG?
Invert the definition: AWG = 36 − (39 ÷ 2) × log(A ÷ A36) ÷ log(92), where A36 is the area of 36 AWG. In practice the converter does it and shows the nearest sizes in both series.
What is kcmil?
A thousand circular mils, a unit of area for large conductors. One kcmil is about 0.5067 mm².
Is 4/0 the same as 0000?
Yes. 4/0 and 0000 are two ways of writing the same size, n = −3.
Sources and constants
- ASTM B258, standard nominal diameters and cross-sectional areas of AWG sizes (the standard itself is paywalled and is not reproduced here)
- IEC 60228, conductors of insulated cables (the standard itself is paywalled and is not reproduced here)