What is voltage drop?
Voltage drop is the voltage lost along the conductors, V_drop = I × R, so it grows with length, current and temperature and shrinks with conductor area.
The idea
A conductor is not a perfect wire. It has a small resistance, and when current flows through it some voltage is used up along the way. What reaches the load is the source voltage minus that drop. Ohm’s law gives the drop: V_drop = I × R, where R is the resistance of the whole loop, out and back.
R = ρ × L ÷ A V_drop = 2 × I × R (DC, out and back)ρ is the resistivity of the metal, L the length of one conductor and A its cross-sectional area. Longer, thinner or hotter conductors, and conductors of a poorer metal, have more resistance.
A worked example
12 V supply, 10 A load, 5 m from source to load, 4 mm² copper at 20 °C. One conductor has a resistance of 21.55 mΩ, the loop 0.0431 Ω. The drop is 0.431 V, or 3.59% of 12 V. The load receives 11.569 V, and 4.31 W is turned into heat in the cable.
At 60 °C the copper resistance is 1.1572 times higher, so the drop becomes 0.499 V (4.16%).
What changes it
| 12 V, 10 A, 5 m, 4 mm² copper, 20 °C | Drop | Percent |
|---|---|---|
| Your example | 0.431 V | 3.59% |
| Twice the run (10 m) | 0.862 V | 7.18% |
| Twice the area (8 mm²) | 0.216 V | 1.80% |
| Twice the current (20 A) | 0.862 V | 7.18% |
| Aluminum instead of copper | 0.707 V | 5.89% |
| Copper at 60 °C | 0.499 V | 4.16% |
Drop is proportional to length and current, and inversely proportional to area. Aluminum has about 1.64 times the resistivity of copper, so for the same size it drops about 1.64 times as much.
Why it matters
Lights get dimmer, motors run hotter, chargers and electronics may switch off when the supply at the load is too low. The right amount of drop depends on the load and the application, and rules and recommended limits differ by country; this guide states none of them. In the calculators the target is a number you choose.
Common mistakes
- Using the one-way length in a formula that expects the loop length, or the reverse. See one-way or round trip.
- Ignoring temperature: warm copper drops more than cold copper.
- Mixing line-to-line and line-to-neutral voltages in three-phase circuits.
- Treating voltage drop and current rating as the same question. A cable can have an acceptable drop and still be too small for its current, or the other way around.
Try it: voltage drop calculator.
Questions
What is a normal voltage drop?
There is no single number. The amount you can accept depends on the load and on the rules where you work, and this guide does not state any limit. In the calculators you choose the target yourself.
Is voltage drop dangerous?
It is a loss of voltage at the load, and the lost energy becomes heat in the conductors. Whether a particular drop is acceptable depends on the equipment and local rules, which is why the calculators show assumptions and make no verdict.
Does a thicker cable always reduce the drop?
Yes, for the same current, length and metal, a larger area lowers the resistance and so lowers the drop in proportion.
Sources and constants
Related
- Voltage drop calculator
- One-way or round trip: which length do you enter?
- mm² vs AWG: how the two size systems relate
Get the app
Want the same numbers on your phone, offline and with your assumptions saved? Gaugewise is a free Android calculator with no ads and no account.
Design aid. Estimates from physics and the values you entered; not a code check. Final wire selection remains the installer's responsibility. Full disclaimer.